Final | 9/27/2006 | 9/27/2006 | 9/27/2006 | P | PASS |
Bob Reichert
|
|
|
dale; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
Final | 8/15/2006 | 8/16/2006 | 8/16/2006 | P | FAIL |
Bob Reichert
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice,nec 314.21 microwave recpt shall be be repaired such that gap to mounting surface is less than 1/8", 410.4(D) fixtures in baths zone of 3' shall be listed for damp location and no chain hung fixtures shall be installed,BCC disposal shall be installed,kitchen recpt shall be finished
|
Electrical Rough-In | 5/16/2006 | 5/17/2006 | 5/17/2006 | A | PASS |
Bob Reichert
|
|
|
###-#### - bill Note: trench u/g ok to cover to outbuilding from house
|
Electrical Rough-In | 4/24/2006 | 4/24/2006 | 4/24/2006 | P | PASS |
Bob Reichert
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Electrical Rough-In | 4/21/2006 | 4/24/2006 | 4/24/2006 | A | FAIL |
Bob Reichert
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, BCC all make-up shall be done, nec 210.52(D) each basin in batf shall have recpt within 3' of basin, 210.52(A) recpt spacing shall be within 12' along wall line in mbr, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 250.86 all metal boxes shall be grounded
|
Permanent Service | 3/15/2006 | 3/15/2006 | 3/15/2006 | P | PASS |
Bob Reichert
|
|
|
###-#### - bill p/s o/h n ok
|