Permit Information
Permit NumberELE06-00892
StatusFinaled
Name MARTELL ELECTRIC
Site Address 2780 N WILDWOOD ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/27/20069/27/20069/27/2006PPASS
DetailsBob Reichert
dale; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
Final8/15/20068/16/20068/16/2006PFAIL
DetailsBob Reichert
bill; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice,nec 314.21 microwave recpt shall be be repaired such that gap to mounting surface is less than 1/8", 410.4(D) fixtures in baths zone of 3' shall be listed for damp location and no chain hung fixtures shall be installed,BCC disposal shall be installed,kitchen recpt shall be finished
Electrical Rough-In5/16/20065/17/20065/17/2006APASS
DetailsBob Reichert
###-#### - bill Note: trench u/g ok to cover to outbuilding from house
Electrical Rough-In4/24/20064/24/20064/24/2006PPASS
DetailsBob Reichert
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
Electrical Rough-In4/21/20064/24/20064/24/2006AFAIL
DetailsBob Reichert
bill; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, BCC all make-up shall be done, nec 210.52(D) each basin in batf shall have recpt within 3' of basin, 210.52(A) recpt spacing shall be within 12' along wall line in mbr, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 250.86 all metal boxes shall be grounded
Permanent Service3/15/20063/15/20063/15/2006PPASS
DetailsBob Reichert
###-#### - bill p/s o/h n ok