Temporary Service | 3/23/2006 | 3/24/2006 | 3/24/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/23/2006 at 3:00:27 PM. Contact: ###-####. corr made, t/s u/g n ok
|
Temporary Service | 3/23/2006 | 3/23/2006 | 3/23/2006 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/23/2006 at 6:56:48 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.53(G) upper end of electrode shall be flush with ground, 250.24(A) grounding electrode conductor shall be connected to grounded conductor terminal, fee due
|