Final | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | PASS |
William E Thomas
|
|
|
Leslie; Phone #: ###-#### Internet Inspection Request from: Darla Downs FINAL OK
|
Electrical Rough-In | 4/6/2006 | 4/7/2006 | 4/7/2006 | A | PASS |
Jack Frank
|
|
|
les; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok shed and house basement
|
Permanent Service | 3/27/2006 | 3/27/2006 | 3/27/2006 | P | PASS |
Jack Frank
|
|
|
leslie -call 1st before insp -late pm if possible; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s o/h rec. ok
|
Permanent Service | 3/24/2006 | 3/27/2006 | 3/27/2006 | A | FAIL |
Jack Frank
|
|
|
Leslie; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corr. met owner 300.10 &12 needs locknuts nipple meter and panel, 314.16 box fill, 110.3 rplace or jbox for damaged romex sheath334.30 staple romex 12" of panel, 330.40 approved fitting for MC, 250.90,92 bond nipple between meter panel,250.148 splice all equip together at jboxes,348.42 shall not conceal 90 degree flex fitting, install guy kit
|
Conference | 3/22/2006 | 3/23/2006 | 3/23/2006 | A | DONE |
Jack Frank
|
|
|
les ###-####- call 1st before insp ok met with owner
|