Final | 5/2/2006 | 5/3/2006 | 5/3/2006 | A | PASS |
Bob Reichert
|
|
|
Trailer Key Taped to Lid of Outside Panel Re-inspection Final Alt Contact ###-####; Phone #: ###-#### Internet Inspection Request from: Cathy Felin called left message, job done, see p/s, ok to final
|
Permanent Service | 3/30/2006 | 3/30/2006 | 3/30/2006 | P | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 3/30/2006 at 9:44:59 AM. Contact: ###-####. p/s o/h reconnect ok
|
Permanent Service | 3/24/2006 | 3/24/2006 | 3/24/2006 | P | FAIL |
Bob Reichert
|
|
|
kelley falin ###-#### or ###-#### called contr, left corr notice,240.81 circuit bkr handle shall be on in up position, 312.5 abrasion protection shall be provided for all conductors entering enclosures,250.24(1) gndg electrode conductor shall connect to grounded conductor terminal, 314.15(A) coupling shall be listed for use in wet location, 230.66 service equip shall be marked to identify as being suitable for use as service equipment
|