Final | 7/28/2006 | 7/28/2006 | 7/28/2006 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot
|
Final | 7/26/2006 | 7/27/2006 | 7/27/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contr, left corr notice, hot tub not on permit, told to change, did not open tub, no access room, nec 110.26 sufficient access and working space shall be provided about all elect equip depth and width, 210.8(A)(3) all outdoor recpts shall be gfci protected, 406.4 recepts shall be securely mounted, rest of elect ok
|
Rough-In Permanent Service | 4/13/2006 | 4/13/2006 | 4/13/2006 | P | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot R/I Ok P/S U/G N Ok
|