Final | 3/30/2006 | 3/31/2006 | 3/31/2006 | A | PASS |
Bob Reichert
|
|
|
please contact Julian, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters see p/s, ok to final
|
Permanent Service | 3/31/2006 | 3/31/2006 | 3/31/2006 | P | PASS |
Bob Reichert
|
|
|
please contact Julian, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr made, p/s exst meter, o/h ok
|
Permanent Service | 3/29/2006 | 3/29/2006 | 3/29/2006 | P | FAIL |
Bob Reichert
|
|
|
miles ###-#### called contr, left corr notice, 358.30(A) conduit shall be supported wihin 3' of box, 230.24(A) exception 3 clearance over roof shall be 18", (B) minimum clearance from grade shall be 10', BCC job id sticker shall be posted
|