Final | 5/30/2006 | 5/31/2006 | 5/31/2006 | A | PASS |
Jack Frank
|
|
|
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
|
Final | 5/24/2006 | 5/25/2006 | 5/25/2006 | A | FAIL |
Jack Frank
|
|
|
MORGAN; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corr. fee due posted called 680.26(B)(1) shall bond all parts of metal (cover track)314.3 shall follow manufactures instructions for plastic box with metallic raceway, 110.3 shall not remove sealing washer from listed R/T emt fittings
|
Electrical Rough-In | 5/3/2006 | 5/4/2006 | 5/4/2006 | P | PART |
Jack Frank
|
|
|
potting and bonding inspection for pool Internet Inspection Request from: Tyler Bowen ok equipotential grid and potting ok
|
Electrical Rough-In | 4/17/2006 | 4/17/2006 | 4/17/2006 | P | PART |
Jack Frank
|
|
|
underground Internet Inspection Request from: Tyler Bowen u/g ok still needs equipotential grid
|
Electrical Rough-In | 4/12/2006 | 4/13/2006 | 4/13/2006 | A | FAIL |
Jack Frank
|
|
|
UNDERGROUND Internet Inspection Request from: Tyler Bowen corr do not cover called 352.26 over 360 degrees of bend in u/g to pool light and out in the yard
|
Electrical Rough-In | 4/4/2006 | 4/5/2006 | 4/5/2006 | A | PART |
Bob Reichert
|
|
|
bonding inspection Internet Inspection Request from: Tyler Bowen looked at pool bond, ok. no u/g for conduit seen.
|