Temporary Service | 4/6/2006 | 4/7/2006 | 4/7/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson t/s u/g new ok
|
Temporary Service | 4/5/2006 | 4/6/2006 | 4/6/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corr. called 250.24(A)(1) terminate GEC too neutral bus, 312.5 needs conn. for GEC
|