Final | 9/26/2007 | 9/27/2007 | 9/27/2007 | A | PASS |
Bob Reichert
|
|
|
jason Phone #: ###-#### corrections made, ok to final
|
Final | 9/20/2007 | 9/21/2007 | 9/21/2007 | P | NR |
Bob Reichert
|
|
|
jason Phone #: ###-#### work covered without inspection, people living in house, checked as many receptacles as could, left list with homeowner to fix before do a final: add dishwasher lockout,get power to receptacles left of sink, clear up and identify panel schedule completely, add globe guards for closet fixtures, add globe guards for closet fixtures, install in-use covers for outside receptacles, add faceplates for dishwasher and microwave, fix open neutral for outside rear receptacle, provide gfci for upstairs bath receptacle, fix upper hallway receptacle in low wall, be sure receptacles are flush with or project from faceplates, owner will fix and call next week
|
Conference | 6/5/2006 | 6/5/2006 | 6/5/2006 | P | DONE |
Bob Reichert
|
|
|
reviewed stapling, box placement, meter height,1 1/4" for nm cable, met with 315
|
Conference | 6/2/2006 | 6/5/2006 | 6/5/2006 | A | DONE |
Jack Frank
|
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met owner, had Bob R do conference with me. Told owner to call if questions on NEC
|
Rough-In Permanent Service | 5/23/2006 | 5/26/2006 | 5/26/2006 | A | FAIL |
Jack Frank
|
|
|
jason appleman; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa Had conference with owner. Did not post correction.
|