Final | 6/14/2006 | 6/15/2006 | 6/15/2006 | A | PASS |
Bob Reichert
|
|
|
LOS BETOS IS READY FOR FINAL RE-INSPECTION. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall corr made, ok to final, signed occ card
|
Final | 6/13/2006 | 6/14/2006 | 6/14/2006 | A | FAIL |
Jack Frank
|
|
|
LOS BETOS RESTAURANT IS READY TO RE-INSPECT. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall still needs gfci and show window outlets called
|
Final | 6/7/2006 | 6/8/2006 | 6/8/2006 | A | FAIL |
Jack Frank
|
|
|
LOS BETOS RESTAURANT IS READY FOR FINAL INSPECTION. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall corr. called left message110.3(B) use manufactures breakers only, 408.4 panel directory, 314.23 secure box floor middle of kit., 210.62 needs show window outlets there is a sign already hanging with no power for itin the window, 210.8(B)(2) gfci for kit,and front couter area with sink, BCC no violations to be retained, note is all equipment at site and wired what are blanked boxes for?
|
Electrical Rough-In | 4/13/2006 | 4/13/2006 | 4/13/2006 | P | PASS |
William E Thomas
|
|
|
See Electrician on site - JOSH - inspect new wall only - box in wall to be covered; Phone #: ###-#### Internet Inspection Request from: Barry Kendall two walls only in back room ok to cover
|