Electrical Rough-In | 4/20/2006 | 4/20/2006 | 4/20/2006 | P | PASS |
Bob Reichert
|
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Electrical Rough-In | 4/19/2006 | 4/19/2006 | 4/19/2006 | P | FAIL |
Bob Reichert
|
|
|
###-#### - lloyd called contr, left message, left corr notice,110.12(C) there shall be no broken parts (box), 300.4(A) & (D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be secured within 8" of box, 210.52(E) there shall be a receptacle in front of house, BCC all make-up shall be done
|