Temporary Service | 4/21/2006 | 4/21/2006 | 4/21/2006 | P | FAIL |
Bob Reichert
|
|
|
greg ###-#### called, left message,left corr notice, nec 230.24(B)(5) service drop conductors shall have minimum 18' clearance from grade over alley, 230.24(A) service drop conductors shall be minimum 8' over roof of building,250.24 grounding electrode conductor shall be connected to grounded conductor terminal, job id sticker shall be filled out, Note: this looks like homeowner permit, but temp pole has TDR lettering.All permits appear to be homeowners.
|