Temporary Service | 4/25/2006 | 4/26/2006 | 4/26/2006 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s u/g n ok
|
Temporary Service | 4/24/2006 | 4/24/2006 | 4/24/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas called contr, left message, left corr notice, 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be provided, Note: pole shall be firmly set, fee due.
|