DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/26/20065/30/20065/30/2006APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 5/26/2006 at 8:22:54 PM. Contact: ###-####. corr made, ok to final
Final5/23/20065/23/20065/23/2006PFAIL
DetailsBob Reichert
ethan - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, nec 210.12(B) all 120v 15 and 20A branch circuits supplying outlets in dwelling unit bedrooms shall be protected by a listed arc-fault circuit interrupter, 314.20 in walls of combustible material box shall be flush with finished surface, 314.21 drywall shall be finished so there are no gaps greater than 1/8", 406.5 faceplates shall be installed to completely cover opening and seat against surface, 406.4(D) recpts shall be flush with or project from faceplates
Electrical Rough-In4/24/20064/25/20064/25/2006APASS
DetailsBob Reichert
###-#### - mitch told contr about 1 1/4" and stapling, he will fix, ric ok, told owner to provide access to panel