Final | 9/21/2006 | 9/22/2006 | 9/22/2006 | A | PASS |
Bob Reichert
|
|
|
gene - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
Rough-In Permanent Service | 5/8/2006 | 5/9/2006 | 5/9/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/8/2006 at 3:17:41 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Electrical Rough-In | 5/8/2006 | 5/8/2006 | 5/8/2006 | P | FAIL |
Bob Reichert
|
|
|
jean; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 314.20 in walls of combustible material, boxes shall be flush with finished surface,314.17(C) nm cable shall be secured within 8" of box,314.27 box shall be supplied for lighting fixture, 300.4(A) &(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A) 2' wall in kitchen shall have recpt, entertainment center shall have 3 recpts per plan, 110.12(C) there shall be no damaged wire, 408.38 panel shall be dead-front,BCC all make-up shall be done
|
Electrical Rough-In | 5/8/2006 | 5/9/2006 | 5/8/2006 | A | CANC |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 5/8/2006 at 3:17:00 PM. Contact: ###-####. called in twice for inspection
|