Temporary Service | 5/30/2006 | 5/31/2006 | 5/31/2006 | A | PASS |
William E Thomas
|
|
|
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy t/s u/g n ok
|
Final | 5/30/2006 | 5/30/2006 | 5/30/2006 | P | CANC |
Bob Reichert
|
|
|
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy wrong type inspection, should be t/s
|
Temporary Service | 5/30/2006 | 5/30/2006 | 5/30/2006 | P | FAIL |
Bob Reichert
|
|
|
TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, left corr notice,nec 240.4(D) maximum overcurrent protection for #12 conductor shall be 20A, 352.30 rnc shall be supported within 3' of panel
|
Final | 5/23/2006 | 5/24/2006 | 5/24/2006 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|