Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE06-01612
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 10689 W USTICK RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Core and shell wiring///final cert of value $62905 per capitol 2/13/2007 cmc
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/9/200610/9/200610/9/2006APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams called to put on permanent sticker for house panel, corr made, ok to final
Electrical Rough-In10/5/200610/5/200610/5/2006AFAIL
DetailsBob Reichert
called elect, BCC no nm cable shall be used in commercial buildings, nec 358.26 there shall not be more than 360 degree bends in emt to rooftops, left corr notice
Permanent Service8/31/20068/31/20068/31/2006PCANC
DetailsWilliam E Thomas
Call first for info; Phone #: ###-#### Internet Inspection Request from: Jim Williams
nothing to inspect
Permanent Service8/15/20068/15/20068/15/2006APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s u/g n ok, house panel only
Electrical Rough-In7/31/20067/31/20067/31/2006PPASS
DetailsJim Schmer
Phone #: ###-#### Internet Inspection Request from: Jim Williams front, east & west walls & 3 bathrooms
Electrical Rough-In6/1/20066/1/20066/1/2006PPASS
DetailsWilliam E Thomas
Underground; Phone #: ###-#### Internet Inspection Request from: Jim Williams
slab on grade underground ok to cover
Electrical Rough-In5/18/20065/18/20065/18/2006PPASS
DetailsBob Reichert
underground; Phone #: ###-#### Internet Inspection Request from: Jim Williams u/g under bldg only ok to cover
Electrical Rough-In5/8/20065/9/20065/9/2006APASS
DetailsBob Reichert
ufer ground
; Phone #: ###-#### Internet Inspection Request from: Jim Williams ok to pour u/g gec