ELE-Aging Inspection | 9/19/2006 | 9/19/2006 | 9/19/2006 | | NR |
Mike Kinnear
|
|
|
no activity
|
ELE-Aging Inspection | 7/18/2006 | 7/18/2006 | 7/18/2006 | | NR |
Mike Kinnear
|
|
|
drove by job site work still going
|
Permanent Service | 5/18/2006 | 5/18/2006 | 5/18/2006 | P | NR |
Mike Kinnear
|
|
|
walt ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie service not ready. no under ground conduit inspection, no grounding electrode, interior panals setting outside in the weather, service panals not completed & pvc conduit in transformer damaged. t/w walt the electrician on job site & advised him of the problems.
|