Final | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | PASS |
Bob Reichert
|
|
|
allan ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final, corrections made
|
Final | 7/5/2006 | 7/5/2006 | 7/5/2006 | P | FAIL |
Bob Reichert
|
|
|
allan - suite 90; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left message, left corr notice, nec 348.30 fmc shall be supported within 12" of box,358.30(A) emt shall be supported within 3' of box, 408.4 circuit directory shall be clear and concise for every circuit, 110.12(A) unused openings in boxes shall be closed,725.3(B) abandoned cl2, cl3, and pltc shall be removed,314.25 each box shall have a cover, 300.11(B) raceways shall not be used as support for other cables BCC no violations shall be retained
|
Electrical Rough-In | 5/18/2006 | 5/18/2006 | 5/18/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 5/18/2006 at 7:00:42 AM. Contact: ###-####. ok to cover new walls only, talked to contractor about no violations shall be retained, we'll inspect to make sure job is up to code at final
|
Rough-In Permanent Service | 5/17/2006 | 5/17/2006 | 5/17/2006 | P | NR |
Bob Reichert
|
|
|
Allen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, said needed plans and probably someone to show what is being done, lots of abandoned cable, 1 1/4 for mc cable, ground metal boxes, told contr no violations shall be retained, told to recall when ready
|