Permanent Service | 5/24/2006 | 5/24/2006 | 5/24/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer corr. not made other violations created electrician shall be at site to remove meter so I can inspect ,shall seal unused opening new one where old GEC removed called left message reinspection fee due added
|
Conference | 5/23/2006 | 5/23/2006 | 5/23/2006 | P | DONE |
Jack Frank
|
|
|
conference ok p/s still all messed up corr. not made met electrician
|
Permanent Service | 5/22/2006 | 5/23/2006 | 5/23/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer corr. called 250.64(C&E) splices in GEC needs listed grd fittings for GEC at meterbase and both ends of nipple250.24 terminate GEC to neutral 230.24(A) needs 8ft over roof, 110.12(A) seal KOs, note sheath of cable not in conn, rigid requires locknuts both inside and outside , remove old GEC that is spliced in panel, is hot and cold bonded, had no acces into meter base, partial correction notice only need too talk with electrician called no response C O W
|
Final | 5/19/2006 | 5/22/2006 | 5/22/2006 | A | NR |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called job not ready, also p/s not final
|