Electrical Rough-In | 6/26/2006 | 6/27/2006 | 6/27/2006 | A | PASS |
Bob Reichert
|
|
|
noble; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Rough-In Permanent Service | 6/22/2006 | 6/26/2006 | 6/26/2006 | A | FAIL |
Bob Reichert
|
|
|
Darrin; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections not made, said to call when done
|
Electrical Rough-In | 6/19/2006 | 6/21/2006 | 6/21/2006 | A | FAIL |
Bob Reichert
|
|
|
victor; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung talked to builder not homeowner,called office, told builder permit voided, since he is not electrician or homeowner. Left corr notice and do not cover sticker, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 in walls of combustible material, boxes shall be flush with finished surface or project therefrom, 300.14 at least 6" free conductor shall be at each box,BCC all make-up shall be done
|