Final | 5/23/2006 | 5/24/2006 | 5/24/2006 | A | CANC |
Bob Reichert
|
|
|
Pat; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt see t/s
|
Temporary Service | 5/24/2006 | 5/24/2006 | 5/24/2006 | A | PASS |
Bob Reichert
|
|
|
Pat; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt corr made, t/s u/g n ok
|
Temporary Service | 5/22/2006 | 5/23/2006 | 5/23/2006 | A | FAIL |
Bob Reichert
|
|
|
joe-- ###-####-- for a temp pole called contr, left corr notice, nec 110.12(A) unused openings shall be closed, 110.12(C) there shall be no broken parts, 230.26 in no case shall service conductors be less than 10' above finished grade, 110.14(A) connections of conductors to terminals shall ensure thoroughly good connections, 110.26(A) work space shall be provided about equipment
|