ELE-Aging Inspection | 8/9/2006 | 8/9/2006 | 8/9/2006 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 8/9/2006 | 8/9/2006 | 8/9/2006 | P | PASS |
Bob Reichert
|
|
|
corr made, ok to final
|
Final | 5/23/2006 | 5/24/2006 | 5/24/2006 | A | CANC |
Bob Reichert
|
|
|
need final inspection on repair of electrical service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH see p/s
|
Permanent Service | 5/24/2006 | 5/24/2006 | 5/24/2006 | A | PASS |
Bob Reichert
|
|
|
need final inspection on repair of electrical service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, nec 408.4 circ directory shall be provided, 358.30(A) emt shall be fastened within 3' of box, 408.3(E) phase arrgmt shall be abc top to bottom, need to call for final after corrections made p/s o/h rec ok
|