Permit NumberELE06-01976
StatusFinaled
Name ELECTRICAL CONTROLS & INSTRUMENT
Site Address 2631 S HAYDEN WAY
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Relocate service to new garage, wire new bath
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/22/20076/26/20076/26/2007PPASS
DetailsBob Reichert
home owner will be home after 11.30 am. new garage, master bath. Phone #: ###-#### Internet Inspection Request from: Shane Vigil ok to final
Electrical Rough-In8/2/20068/7/20068/7/2006APASS
DetailsJack Frank
8 Am if you can. Please contact home owner for access to house for bath and landry. Craig at ###-#### ; Phone #: ###-#### Internet Inspection Request from: Shane Vigil r/i ok bath laundry and garage ok
Permanent Service6/1/20066/2/20066/2/2006APASS
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: Shane Vigil p/s u/g reconnect ok note called ri not ready yet will call for inspection when done.
Permanent Service5/31/20066/1/20066/1/2006AFAIL
DetailsJack Frank
please call if you have ?'s ; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corr called 110.3(A)6 &12(C) replace panel bus damaged from arcing 110.12(A) seal KOs panel, 250.24(A)(1) treminate all bonds AND GEC to neutral bus 110.(A&B) install manufactures bond screw, 334.80 if over 2 cables per hole derate, 300.4(A)(1&2) nail plates note if attic access is in garage protect cables within 6ft