Final | 6/22/2007 | 6/26/2007 | 6/26/2007 | P | PASS |
Bob Reichert
|
|
|
home owner will be home after 11.30 am. new garage, master bath. Phone #: ###-#### Internet Inspection Request from: Shane Vigil ok to final
|
Electrical Rough-In | 8/2/2006 | 8/7/2006 | 8/7/2006 | A | PASS |
Jack Frank
|
|
|
8 Am if you can. Please contact home owner for access to house for bath and landry. Craig at ###-#### ; Phone #: ###-#### Internet Inspection Request from: Shane Vigil r/i ok bath laundry and garage ok
|
Permanent Service | 6/1/2006 | 6/2/2006 | 6/2/2006 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shane Vigil p/s u/g reconnect ok note called ri not ready yet will call for inspection when done.
|
Permanent Service | 5/31/2006 | 6/1/2006 | 6/1/2006 | A | FAIL |
Jack Frank
|
|
|
please call if you have ?'s ; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corr called 110.3(A)6 &12(C) replace panel bus damaged from arcing 110.12(A) seal KOs panel, 250.24(A)(1) treminate all bonds AND GEC to neutral bus 110.(A&B) install manufactures bond screw, 334.80 if over 2 cables per hole derate, 300.4(A)(1&2) nail plates note if attic access is in garage protect cables within 6ft
|