Final | 8/15/2006 | 8/16/2006 | 8/16/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman corr made, ok to final, signed card
|
Final | 8/15/2006 | 8/15/2006 | 8/15/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 314.23(B) box shall be rigidly supported by structural member, 358.30(A) emt shall be supported within 3' of box and or termination, 348.30(A) fmc shall be supported within 12" of box, 110.3(A) transformer shall be listed as an approved j-box or pull-box,110.3(B) equipment shall be installed per instructions in listing, BCC listing shall be provided for compressor, wiring shall be per mfgrs instructions
|
Permanent Service | 7/12/2006 | 7/13/2006 | 7/13/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman p/s exst meter pak, n ok
|
Electrical Rough-In | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | PASS |
Bob Reichert
|
|
|
ceiling and service inspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ceiling only ok to cover
|
Electrical Rough-In | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PASS |
Bob Reichert
|
|
|
ceiling inspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman ok to cover hard lids only
|
Electrical Rough-In | 6/5/2006 | 6/6/2006 | 6/6/2006 | P | PASS |
Bob Reichert
|
|
|
We need a wall inspection ; Phone #: ###-#### Internet Inspection Request from: DJ Carman walls only, soffit, and u/g ok to cover
|