Final | 7/27/2006 | 7/28/2006 | 7/28/2006 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/27/2006 at 2:20:27 PM. Contact: ###-####.
|
Rough-In Permanent Service | 6/13/2006 | 6/14/2006 | 6/14/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/13/2006 at 11:46:38 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/9/2006 | 6/13/2006 | 6/13/2006 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/9/2006 at 10:19:04 AM. Contact: ###-####. talked to contr, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member,334.80 more than 2 nm cables shall be derated per 310.15(B)(2) that are bundled through wood framing that is to be draft stopped
|