Final | 6/16/2006 | 6/16/2006 | 6/16/2006 | P | PASS |
Jack Frank
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed
|
Electrical Rough-In | 6/5/2006 | 6/6/2006 | 6/6/2006 | A | PART |
Jack Frank
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Cathy r/i walls ok
|
Electrical Rough-In | 6/2/2006 | 6/2/2006 | 6/2/2006 | P | FAIL |
Jack Frank
|
|
|
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley all violations not corrected, called Ted no answer and could not leave message recording said no space left on recorder to leave message
|
Electrical Rough-In | 6/1/2006 | 6/2/2006 | 6/2/2006 | A | FAIL |
Bob Reichert
|
|
|
dennis kelley; Phone #: ###-#### Internet Inspection Request from: Darla Downs met elect, told to call and change name on permit, nec 300.4(D) mc shall be 1 1/4" from edge of framing member, 330.30(B) mc shall be supported within 12" of box, 300.11(A) no low voltage shall be supported by ceiling grid or support wires,BCC approved set of plans shall be on job, left corr notice with elect in office #152
|