Final | 11/7/2006 | 11/8/2006 | 11/8/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called contr to tighten gnd clamps and add screw to box, ok to final, signed occ card
|
Electrical Rough-In | 10/16/2006 | 10/17/2006 | 10/17/2006 | A | PASS |
Bob Reichert
|
|
|
inspection for light pole in parking lot and under ground conduit; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS u/g ok to cover, parking lot lite
|
Electrical Rough-In | 10/16/2006 | 10/16/2006 | 10/16/2006 | P | CANC |
Bob Reichert
|
|
|
jeremy Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: ERIC CENTERS
|
Permanent Service | 9/25/2006 | 9/26/2006 | 9/26/2006 | A | PASS |
Jack Frank
|
|
|
idaho power will be opening transformer at 10am so we can pull in feeders, need inspection on service to energize. thanks; Phone #: ###-#### Internet Inspection Request from: ERIC p/s u/g new ok
|
Electrical Rough-In | 8/28/2006 | 8/28/2006 | 8/28/2006 | P | PASS |
Jack Frank
|
|
|
eric - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley high and low voltage ok walls and ceilings
|
Electrical Rough-In | 8/23/2006 | 8/24/2006 | 8/24/2006 | A | FAIL |
Jack Frank
|
|
|
Eric; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections not made called still needs nail plates, and use listed conn. for low voltage cable not emt conn.
|
Electrical Rough-In | 8/21/2006 | 8/21/2006 | 8/21/2006 | P | FAIL |
Jack Frank
|
|
|
rock - wall insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called 300.4 nail plates and 11/4" for cables and ent, 250.148 grd all metal boxes,, corr. low voltage bld05-03335 nail plates, 11/4", connectors for all cables, secure cables
|
Electrical Rough-In | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | PASS |
Mike Kinnear
|
|
|
Dirt cover for electrode; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok cover with dirt
|
Electrical Rough-In | 6/5/2006 | 6/6/2006 | 6/6/2006 | A | PASS |
William E Thomas
|
|
|
This is a concrete encased electrode inspection. (rough-in); Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to cover with concrete
|
Electrical Rough-In | 6/2/2006 | 6/2/2006 | 6/2/2006 | P | FAIL |
Jack Frank
|
|
|
Eric, concrete encased electrode; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called concrete encased electrode not allowed inside of building explained it to contractor he will correct
|
Conference | 6/2/2006 | 6/2/2006 | 6/2/2006 | P | CANC |
Jack Frank
|
|
|
Eric, UFER ground inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt - Jack Frank wanted to change from conference to rough in, so canceled this
|