Permit Information
Permit NumberELE06-02020
StatusFinaled
Name CENTERS ELECTRIC
Site Address 10233 W OVERLAND RD
Project NameWalker Dental
Customer Number 
ePlanReview 
Description
Lights, receptacles, switches, service - $57,712 ///Final value is $45,000//1/31/07 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/7/200611/8/200611/8/2006APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called contr to tighten gnd clamps and add screw to box, ok to final, signed occ card
Electrical Rough-In10/16/200610/17/200610/17/2006APASS
DetailsBob Reichert
inspection for light pole in parking lot and under ground conduit; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS u/g ok to cover, parking lot lite
Electrical Rough-In10/16/200610/16/200610/16/2006PCANC
DetailsBob Reichert
jeremy Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection cancelled from web by: ERIC CENTERS
Permanent Service9/25/20069/26/20069/26/2006APASS
DetailsJack Frank
idaho power will be opening transformer at 10am so we can pull in feeders, need inspection on service to energize. thanks; Phone #: ###-#### Internet Inspection Request from: ERIC p/s u/g new ok
Electrical Rough-In8/28/20068/28/20068/28/2006PPASS
DetailsJack Frank
eric - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
high and low voltage ok walls and ceilings
Electrical Rough-In8/23/20068/24/20068/24/2006AFAIL
DetailsJack Frank
Eric; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corrections not made called still needs nail plates, and use listed conn. for low voltage cable not emt conn.
Electrical Rough-In8/21/20068/21/20068/21/2006PFAIL
DetailsJack Frank
rock - wall insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
corr. called 300.4 nail plates and 11/4" for cables and ent, 250.148 grd all metal boxes,, corr. low voltage bld05-03335 nail plates, 11/4", connectors for all cables, secure cables
Electrical Rough-In6/6/20066/7/20066/7/2006APASS
DetailsMike Kinnear
Dirt cover for electrode; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok cover with dirt
Electrical Rough-In6/5/20066/6/20066/6/2006APASS
DetailsWilliam E Thomas
This is a concrete encased electrode inspection. (rough-in); Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS
ok to cover with concrete
Electrical Rough-In6/2/20066/2/20066/2/2006PFAIL
DetailsJack Frank
Eric, concrete encased electrode; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called concrete encased electrode not allowed inside of building explained it to contractor he will correct
Conference6/2/20066/2/20066/2/2006PCANC
DetailsJack Frank
Eric, UFER ground inspection; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt - Jack Frank wanted to change from conference to rough in, so canceled this