Final | 6/7/2006 | 6/8/2006 | 6/8/2006 | A | PASS |
Bob Reichert
|
|
|
bill ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie service ok, u/g ok corr made, ok to final
|
Permanent Service | 6/6/2006 | 6/6/2006 | 6/6/2006 | P | FAIL |
Bob Reichert
|
|
|
bill ###-#### called contr left corr notice,nec 300.5 u/g cable shall be 24" deep, 312.5 abrasion protection shall be provided forr all conductors entering enclosures, 314.15(A) fittings installed in wet locations shall be listed for use in wet locations,BCC no cover shall be done prior to inspection
|