Final | 11/21/2006 | 11/21/2006 | 11/21/2006 | P | PASS |
Jack Frank
|
|
|
mike ###-#### ok
|
Electrical Rough-In | 6/9/2006 | 6/9/2006 | 6/9/2006 | P | PASS |
William E Thomas
|
|
|
mike - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 1. ri ok 2. p/s u/g n ok per insp #370
|
Rough-In Permanent Service | 6/7/2006 | 6/9/2006 | 6/9/2006 | A | FAIL |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice, nec 334.30 nm cable shall be supported within 12" of box (lv), 352.30(A) rnc shall be supported within 3' of box (lv), 210.52(A)(1) recpts shall be installed such that no point is over 6' from recpt outlet,210.52(A)(2) recpt shall be in 2' wall space by dr,BCC all make-up shall be done,approved set of plans shall be on job
|