Permit Information
Permit NumberELE06-02088
StatusFinaled
Name S & M ELECTRIC
Site Address 11673 W ARDYCE ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/21/200611/21/200611/21/2006PPASS
DetailsJack Frank
mike ###-#### ok
Electrical Rough-In6/9/20066/9/20066/9/2006PPASS
DetailsWilliam E Thomas
mike - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
1. ri ok
2. p/s u/g n ok per insp #370
Rough-In Permanent Service6/7/20066/9/20066/9/2006AFAIL
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice, nec 334.30 nm cable shall be supported within 12" of box (lv), 352.30(A) rnc shall be supported within 3' of box (lv), 210.52(A)(1) recpts shall be installed such that no point is over 6' from recpt outlet,210.52(A)(2) recpt shall be in 2' wall space by dr,BCC all make-up shall be done,approved set of plans shall be on job