DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/26/20067/26/20067/26/2006PPASS
DetailsBob Reichert
shawn; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
Final7/25/20067/25/20067/25/2006PFAIL
DetailsBob Reichert
Shawn; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, left corr notice, nec 422.16(B)(2)&(4) built in dishwasher shall shall not use cord over 4' long and recpt shall be in same space, 400.5(A) seo cord ampacity 13 amps, 408.4 circuit directory shall be complete and explicit as to each circuit,314.25 each box shall have a cover, 406.5 recpt faceplates shall seat against mounting surface, 406.4 recpts shall be securely fastened in place
Electrical Rough-In6/7/20066/8/20066/8/2006PCANC
DetailsBob Reichert
###-#### - shawn wrong request, see rip
Rough-In Permanent Service6/7/20066/8/20066/8/2006PPASS
DetailsBob Reichert
###-#### - shawn ric ok p/s u/g n ok