Permit Information
Permit NumberELE06-02093
StatusFinaled
Name PRO-TEC SYSTEMS
Site Address 8730 W OAKMONT DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/18/20069/19/20069/19/2006APASS
DetailsPat Lass
wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Rough-In Permanent Service6/16/20066/19/20066/19/2006APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/16/2006 at 4:22:35 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
Rough-In Permanent Service6/12/20066/12/20066/12/2006PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/12/2006 at 10:52:43 AM. Contact: ###-####. corrections not complete, called contr, will recall
Rough-In Permanent Service6/7/20066/8/20066/8/2006AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/7/2006 at 12:05:29 PM. Contact: ###-####. called contr, left corr notice, nec 250.56 rod electrode shall be augmented by additional electrode, Note: access required to panel, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 334.80 where more than 2 nm cables are bundled through hole to be draft stopped, they shall be derated, 314.16 boxes shall be sufficient size to provide free space for all conductors,314.20 boxes in combustible walls shall be flush with finished surface, 314.27 box shall be installed for luminaire(back door), BCC all make-up shall be done, Note: tub access shall be min 20" w x 15" h