Temporary Service | 6/9/2006 | 6/9/2006 | 6/9/2006 | A | PASS |
Bob Reichert
|
|
|
corr made, t/s u/g n ok
|
Temporary Service | 6/7/2006 | 6/8/2006 | 6/8/2006 | A | FAIL |
Bob Reichert
|
|
|
###-#### - brandon called, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection,110.14(A) connection of conductors to terminal parts shall ensure a thoroughly good connection, 110.3(B) listed or labelled equipment shall be installed and used in accordance with instructions
|