Final | 6/9/2006 | 6/9/2006 | 6/9/2006 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Permanent Service | 6/9/2006 | 6/9/2006 | 6/9/2006 | P | PASS |
Bob Reichert
|
|
|
pat; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, p/s o/h n ok
|
Final | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | CANC |
Bob Reichert
|
|
|
Brenda ###-#### see p/s
|
Permanent Service | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | FAIL |
Bob Reichert
|
|
|
Brenda ###-#### talked w/ owner, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be provided, 590.6(B)(1)gfci protection shall be provided for 50A recpt
|