Final | 1/22/2007 | 1/22/2007 | 1/22/2007 | P | PASS |
Bob Reichert
|
|
|
herbert; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
Electrical Rough-In | 10/6/2006 | 10/6/2006 | 10/6/2006 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/6/2006 at 8:13:00 AM. Contact: ###-####. ok
|
Electrical Rough-In | 7/27/2006 | 7/27/2006 | 7/27/2006 | P | FAIL |
Jack Frank
|
|
|
herb; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr met owner use manufactures listed breakers, 300.4 nail plates and 11/4", 6" free conductor, boxes shall be flush outside, back feed clip for shop main, conn for GEC needs 2 grd rods, complete all make up isolate neutral at shop p/s, do not mix #14and 12 thhn open in wall below garage panel , uncover u/g covered before inspection
|