Final | 7/27/2006 | 7/28/2006 | 7/28/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/27/2006 at 2:19:55 PM. Contact: ###-####. ok to final
|
Rough-In Permanent Service | 6/13/2006 | 6/14/2006 | 6/14/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/13/2006 at 11:45:54 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/9/2006 | 6/13/2006 | 6/13/2006 | A | FAIL |
Bob Reichert
|
|
|
###-#### - steve talked to contr, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, BCC all make-up shall be done
|