Final | 4/1/2008 | 4/1/2008 | 4/1/2008 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Permanent Service | 6/26/2006 | 6/26/2006 | 6/26/2006 | P | PASS |
Jack Frank
|
|
|
ben; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|
Permanent Service | 6/26/2006 | 6/26/2006 | 6/26/2006 | P | PASS |
Jack Frank
|
|
|
ben; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|
Permanent Service | 6/19/2006 | 6/20/2006 | 6/20/2006 | A | PASS |
Jack Frank
|
|
|
ben; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h rec. ok
|
Permanent Service | 6/19/2006 | 6/19/2006 | 6/19/2006 | P | FAIL |
Jack Frank
|
|
|
Ben; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corr. called 110.26(A)(1) shall provide clearence for subpanel needs to be lower, 230.24(A) needs 8ft over garage, 312.5 conn. for GEC, 408.4 panel directory, 110.12 seal ko 4sg ceiling basement, power ok if clearence over garage is corrected, then other corrections shall be made before final
|
Permanent Service | 6/14/2006 | 6/18/2006 | 6/19/2006 | A | CANC |
Jack Frank
|
|
|
ben ###-####
|