Final | 12/27/2006 | 12/27/2006 | 12/27/2006 | P | PASS |
Jack Frank
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Rough-In Permanent Service | 6/19/2006 | 6/19/2006 | 6/19/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/19/2006 at 6:43:42 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/15/2006 | 6/16/2006 | 6/16/2006 | A | FAIL |
Bob Reichert
|
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice,nec 250.64(C)&(D) gec shall be continuous or tapped outside enclosure, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 334.23 nm cable shall comply with 320.23 in attic space, BCC all make-up shall be done,boxes installed,approved set of plans on job. Note: 38 rooms
|