Electrical Rough-In | 6/29/2006 | 6/30/2006 | 6/30/2006 | A | CANC |
Mike Kinnear
|
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley wrong type inspection
|
Final | 6/30/2006 | 6/30/2006 | 6/30/2006 | P | PASS |
Mike Kinnear
|
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok final
|
Permanent Service | 6/30/2006 | 6/30/2006 | 6/30/2006 | P | PASS |
Mike Kinnear
|
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h reconnect ok note corrections made
|
Electrical Rough-In | 6/23/2006 | 6/26/2006 | 6/26/2006 | A | FAIL |
Jack Frank
|
|
|
daniel- call 1/2 hr prior for access-reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. not made still needs to connect to existing grd rod in a mannor approved by NEC called left messages no response back
|
Electrical Rough-In | 6/20/2006 | 6/21/2006 | 6/21/2006 | P | FAIL |
Jack Frank
|
|
|
daniel - call 1/2 hr prior for access reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. fee due called,250.24 all GEC and water bonds shall be at p/s not subpanel, 250.52(A)(1)or 104(A)(1) grd or bond water system, 250.53(G) grd rods shall be 6ft apart, 250.50 where present all electrodes shall be bonded together (old grd rod left of back porch, 250.64(C) shall not splice GEC and remove it from conduit and the subpanel
|
Electrical Rough-In | 6/16/2006 | 6/19/2006 | 6/19/2006 | A | FAIL |
Jack Frank
|
|
|
molly - ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called 250.24 all GEC at p/s not subpanel, isolate grds and neutrals at subpanel 250.52&104 (A)(1) grd or bond water, install 2 grd rods
|
Electrical Rough-In | 6/16/2006 | 6/16/2006 | 6/16/2006 | P | NH |
Jack Frank
|
|
|
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles notice posted called
|