Final | 10/2/2006 | 10/3/2006 | 10/3/2006 | A | PASS |
Pat Lass
|
|
|
Garage code is 2345; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
|
Rough-In Permanent Service | 6/20/2006 | 6/21/2006 | 6/21/2006 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/19/2006 | 6/19/2006 | 6/19/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called, left corr notice, nec 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of holes and nm cable shall be 11/4" from edge of framing member,210.52(E) at least 1 outdoor outlet shall be at front of dwelling,BCC all make-up shall be done and boxes mounted
|