Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE06-02298
StatusFinaled
Name M & J ELECTRIC
Site Address 9550 W MARTINGALE DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/22/200710/22/200710/22/2007PPASS
DetailsBob Reichert
marv Phone #: ###-#### ok to final
Rough-In Permanent Service10/1/200710/2/200710/2/2007PPASS
DetailsBob Reichert
marv - please call 1/2 hr prior to inspection Phone #: ###-#### ri ok for service areas only, will doe areas of ri for house later, p/s u/g n ok
Final8/28/20078/29/20078/29/2007AFAIL
DetailsJack Frank
Marv; Phone #: ###-#### Internet Inspection Request from: Hattie James corr not made and no power meter not set
Electrical Rough-In9/7/20069/7/20069/7/2006PPASS
DetailsBob Reichert
marv Note: groundwork; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to pour gec, will pour slab on top at same time so no backfill inspection required
Permanent Service8/3/20068/3/20068/3/2006PFAIL
DetailsJack Frank
###-#### - marv 250.52(A)(1)or104(A)(1) grd or bond water sized too T250.66, #2 cu 250.90,92 use bond bushing not bonding locknut, where concentrics are encountered, 250.64(E) use listed or plastic fitting for GEC not 3/8 romex conn., 314.28 j box above service disconnects shall be of large enough size for straight pulls, 312.5(C) exception pvc tob of jbox shall meet rquirements of code noted terminate service wirs to far right panel to main breaker not main lugs use backfed device cow