Final | 10/22/2007 | 10/22/2007 | 10/22/2007 | P | PASS |
Bob Reichert
|
|
|
marv Phone #: ###-#### ok to final
|
Rough-In Permanent Service | 10/1/2007 | 10/2/2007 | 10/2/2007 | P | PASS |
Bob Reichert
|
|
|
marv - please call 1/2 hr prior to inspection Phone #: ###-#### ri ok for service areas only, will doe areas of ri for house later, p/s u/g n ok
|
Final | 8/28/2007 | 8/29/2007 | 8/29/2007 | A | FAIL |
Jack Frank
|
|
|
Marv; Phone #: ###-#### Internet Inspection Request from: Hattie James corr not made and no power meter not set
|
Electrical Rough-In | 9/7/2006 | 9/7/2006 | 9/7/2006 | P | PASS |
Bob Reichert
|
|
|
marv Note: groundwork; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to pour gec, will pour slab on top at same time so no backfill inspection required
|
Permanent Service | 8/3/2006 | 8/3/2006 | 8/3/2006 | P | FAIL |
Jack Frank
|
|
|
###-#### - marv 250.52(A)(1)or104(A)(1) grd or bond water sized too T250.66, #2 cu 250.90,92 use bond bushing not bonding locknut, where concentrics are encountered, 250.64(E) use listed or plastic fitting for GEC not 3/8 romex conn., 314.28 j box above service disconnects shall be of large enough size for straight pulls, 312.5(C) exception pvc tob of jbox shall meet rquirements of code noted terminate service wirs to far right panel to main breaker not main lugs use backfed device cow
|