Final | 8/8/2006 | 8/9/2006 | 8/9/2006 | A | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final, signed card, called contr, left message, survey for loose box in closet
|
Electrical Rough-In | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Electrical Rough-In | 6/26/2006 | 6/27/2006 | 6/27/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/26/2006 at 2:17:18 PM. Contact: ###-####. corr. not made called
|
Electrical Rough-In | 6/23/2006 | 6/23/2006 | 6/23/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Please call 30 min prior to going. Internet Inspection Request from: Rita DeYoung called, left messages, left corr notice, nec 330.30(B) mc cable shall be secured within 12" of boxes, 300.4(D) edge of cable shall be 1 1/4" from edge of framing members (includes raceways), 362.30(A) ent shall be fastened at 3' intervals,Note: no wiring in valley of studs
|