Electrical Rough-In | 7/21/2006 | 7/21/2006 | 7/21/2006 | P | PASS |
Bob Reichert
|
|
|
tim ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, called owner to staple nm in 2 places, ric ok
|
Electrical Rough-In | 7/6/2006 | 7/6/2006 | 7/6/2006 | P | FAIL |
Jack Frank
|
|
|
tim- call prior for access - ###-#### Internet Inspection Request from: Barbara Buckley corr. met owner, not all violations made and new ones created, 314.16 box fill, 314.43 nails inside plastic boxes outside recepts, 314.20 boxes still not flush with siding, 300.14 free length of conductor owner cut wires short after Bob's inspection, 110.14 needs devices for all splices just twisted wires note told owner to check all locations for box fill not just one box I found
|
Electrical Rough-In | 7/3/2006 | 7/3/2006 | 7/3/2006 | P | FAIL |
Bob Reichert
|
|
|
tim - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left corr notice, nec 300.4(A)&(D) edgr of holes and nm cable shall be 1 1/4" from edge of framing members,314.20 in walls of combustible material, box shall be flush with finished surface,334.30 nm cable shall be stapled within 12" of box and every 4 1/2', 250.86 metal boxes shall be grounded, 334.80 2 or more nm cables in hole to be draft stopped shall be derated per 310.15(B)(2)(a), BCC all make-up shall be done
|