Final | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | PASS |
Jack Frank
|
|
|
Please call my Journey man a half an hour before he will be on the job, so he can meet the inspector on the job. His name is Jeff Phone # ###-####. Thank you!!; Phone #: ###-#### Internet Inspection Request from: Danette Brookshire ok
|
Final | 10/30/2006 | 10/31/2006 | 10/31/2006 | A | FAIL |
Jack Frank
|
|
|
oga; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles fee due corr. met contr. 314.16 box fill peninsular counter, 408.4 needs specific panel directory, 410.8 clearence MB closet, 314.17 sheath shall enter box ,they had 7" of exposed wire hidden in the wall M bath vanity lights
|
Electrical Rough-In | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | PASS |
Mike Kinnear
|
|
|
Olga; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok cover ri
|
Permanent Service | 6/28/2006 | 6/28/2006 | 6/28/2006 | P | PASS |
Mike Kinnear
|
|
|
Olga; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g n ok
|
Rough-In Permanent Service | 6/26/2006 | 6/27/2006 | 6/27/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire called, left corr notice, 300.4(A)(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 312.5 all conductors shall have abrasion protection, 110.12(A) unused openings in box shall be closed, 110.12(C) there shall be no damaged cable, 210.52(A) recpts shall be spaced 12' along floor line
|