Final | 9/23/2008 | 9/23/2008 | 9/23/2008 | A | PASS |
Bob Reichert
|
|
|
ok to final, no esc this project
|
Permanent Service | 7/17/2006 | 7/18/2006 | 7/18/2006 | A | PASS |
Bob Reichert
|
|
|
back wall of big shop - outside --- ###-#### -jeff ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, p/s o/h n ok
|
Rough-In Permanent Service | 6/27/2006 | 6/28/2006 | 6/28/2006 | A | FAIL |
Bob Reichert
|
|
|
cynthia chandler ###-#### met owner, left corr notice, nec 250.56 single gec shall be augmented by additional electrode,110.12(A) unused openings shall be closed to afford substantially equivalent protection as wall of enclosure, 230.24(B)(2) service shall be min 12' above grade at lowest point, 408.4 circuit directory shall be complete and accurate, 250.64(C) gec shall be continuous, BCC approved set of plans shall be on job and available
|