Final | 11/6/2006 | 11/7/2006 | 11/7/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terrie Dickson ok
|
Final | 9/21/2006 | 9/21/2006 | 9/21/2006 | P | FAIL |
Jack Frank
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called 300.4(A)(1)&(D) for flex, 250.24(A)(1) & 110.3(B) shall terminate all GEC at neutral bus not equip grd bus, need power to building for final
|
Final | 9/15/2006 | 9/18/2006 | 9/18/2006 | A | FAIL |
Jack Frank
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. fee due called left message, 110.3)B) shall follow manufactures instructions , p/s disconnect olny service rated if manufactures neutral kit is used, xformer shall be grd as 250.30 states, 250.52(A)(1) shall bond all piping together so it is electrically continuous, BCC shall not use romex for commercial work
|
Rough-In Permanent Service | 7/19/2006 | 7/19/2006 | 7/19/2006 | P | PASS |
Jim Schmer
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
Rough-In Permanent Service | 7/19/2006 | 7/19/2006 | 7/19/2006 | P | PASS |
Jim Schmer
|
|
|
p/s u/g new -- west of 11393 aldershot in small shed JMS
|
Electrical Rough-In | 7/14/2006 | 7/17/2006 | 7/17/2006 | A | FAIL |
Pat Lass
|
|
|
TERRY ###-#### seperatly derived system not grounded ground rods not 6 ft appart and at less than 45 deg. water not hit for electrode within 5 ft no connectors on electrode conductors
|
Electrical Rough-In | 7/10/2006 | 7/11/2006 | 7/11/2006 | A | NR |
Pat Lass
|
|
|
TERRY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no access
|
Final | 7/7/2006 | 7/7/2006 | 7/7/2006 | P | CANC |
Jack Frank
|
|
|
TERRY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong address and street name new subdivision no street sign, no nothing called contractor will contact planning and zoning , and addressing for correct number and street
|