ELE-Request for Extension | 8/9/2007 | 8/9/2007 | 8/9/2007 | P | PASS |
Jim Schmer
|
|
|
will request final probably next week//Shawn ###-#### ok jms
|
Permanent Service | 7/13/2006 | 7/13/2006 | 7/13/2006 | P | PASS |
Mike Kinnear
|
|
|
sean ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s o/h reconnect ok
|
Electrical Rough-In | 7/10/2006 | 7/11/2006 | 7/11/2006 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 7/10/2006 at 9:31:10 PM. Contact: ###-####. ok cover ri
|
Electrical Rough-In | 7/5/2006 | 7/6/2006 | 7/6/2006 | A | FAIL |
Jack Frank
|
|
|
wall r/i --shawn ###-#### cell corr. called left message300.4 nail plates & 11/4", 314.16 box fill new plastic cutin and old steel boxes, 314.25(D) needs listed fan boxes, 314.20 boxes shall be flush with combustible material, set back no more than 1/4 in other, 210.52(A) outlet spacing din rm & room north of din. rm 250.148 grd metal boxes, note cable sheath shall extend into box S W bed rm cable for outside recept, check for correct small appliance branch circuits
|