Final | 8/28/2006 | 8/28/2006 | 8/28/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/28/2006 at 6:31:11 AM. Contact: ###-####. ok to final
|
Final | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | FAIL |
Bob Reichert
|
|
|
Internet Inspection Request from: Rowdy Monroe called left corr notice, nec 422.31(B) disconnect shall be supplied for heater, 110.3 gfci left of stove shall operate,BCC access shall be provided inside panel
|
Electrical Rough-In | 7/10/2006 | 7/11/2006 | 7/11/2006 | A | PASS |
Bob Reichert
|
|
|
rough reinspect Internet Inspection Request from: Rowdy Monroe corr made, ric ok
|
Rough-In Permanent Service | 7/10/2006 | 7/10/2006 | 7/10/2006 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/10/2006 at 5:33:07 AM. Contact: ###-####. p/s u/g n ok, called on ri, nec 300.4(D) nm cable shall be 1 1/4" from edge of framing member,314.20 boxes shall be flush in walls of combustible material, 210.52(A) shall add recpt to 2' wall by hall to bedrooms, BCC all make-up shall be done
|