DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/28/20068/28/20068/28/2006PPASS
DetailsBob Reichert
###-#### - nick called left survey, nec 210.8(A) garage gfci shall operate,422.31(B) dishwasher shall have lockout, 408.4 circuit directory shall be complete and explanatory,BCC bath recpt shall be trimmed
Electrical Rough-In7/11/20067/11/20067/11/2006PCANC
DetailsBob Reichert
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see rip, wrong type inspection
Rough-In Permanent Service7/11/20067/11/20067/11/2006PPASS
DetailsBob Reichert
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok
Rough-In Permanent Service7/10/20067/10/20067/10/2006PNR
DetailsPat Lass
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
no print on job
nail plates missing mis circuited kitchen, electrode not connected to neutral bus