Permit Information
Permit NumberELE06-02543
StatusFinaled
Name WHITE CLOUD ELECTRIC
Site Address 2712 N COLUMBINE AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/19/200610/19/200610/19/2006PPASS
DetailsMike Kinnear
spencer; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made ok final
Final10/2/200610/3/200610/3/2006AFAIL
DetailsBob Reichert
steven; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called left message, nec 210.8(A)(7) laundry recpt shall be gfci protected if within 6' of sink, 210.52(A)(2) recpt shall be installed in 2' wall by kitchen/dining room, BCC all trim shall be done, baths, address shall be posted
Electrical Rough-In7/19/20067/19/20067/19/2006PCANC
DetailsBob Reichert
shelly ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see rip, wrong insp request
Rough-In Permanent Service7/19/20067/19/20067/19/2006PPASS
DetailsBob Reichert
shelly ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr to add 1 recpt in nook and check outside gar recpt due to siders blocking access. ric ok, p/s u/g n ok